feat(interconnect): add the inverter certification and settings reference, each value cited to the sheet that prints it
/interconnect/inverter-settings/ explains UL 1741 SB against the earlier SA. It cites PG&E's Rule 21 § Hh, which writes its requirements to SB with IEEE 1547-2018 as the source, and Hawaiian Electric's Rule 14, which has required IEEE 1547-2018 certification since February 2023. It leaves acceptance of older equipment to the authority having jurisdiction and the utility. California's frequency trip, volt-VAR, volt-watt, and default activation settings are given in our own grouping, by what each setting does for a project, and every value is found in the stored capture of the Rule 21 sheet it cites. Hawaii's rule points to its Utility-Required Profile, and the page shows no California numbers for it. The voltage trip and ride-through settings, printed in Rule 21 only as images, and the reactive capability values are omitted, naming where IEEE 1547-2018 defines them. The page states that the standard's text is not reproduced, and the inverter sizing tool links it. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
1 parent fa34758 commit 0a1e52b

11 files changed

Lines changed: 254 additions & 4 deletions

File tree

Lines changed: 11 additions & 0 deletions
Original file line numberDiff line numberDiff line change
@@ -0,0 +1,11 @@
1+
Source: https://www.hawaiianelectric.com/documents/billing_and_payment/rates/hawaiian_electric_rules/14.pdf
2+
Publisher: Hawaiian Electric Company, Inc., Rule No. 14 (Service Connections and Facilities on Customer's Premises), Appendix I (Interconnection Technical Requirements)
3+
Retrieved: 2026-11-21
4+
Original: 3488331 bytes, SHA-256 ee8ac69b350003f8a27f5be9447dbdd28a8ef825ceb4c9cd4a14c448fcc3a590
5+
Capture: the definition of the Utility-Required Profile and the certification paragraphs of Appendix I, as pdftotext -layout reads them, whitespace collapsed
6+
----
7+
[Rule 14 Appendix I, definition y, Utility-Required Profile]
8+
y. Utility-Required Profile (“URP”): Full set of configuration parameters that establish the behavior of a DER arranged in a single electronic file in a standardized format.
9+
10+
[Rule 14 Appendix I, equipment certification]
11+
inverter-based Generating Facilities, which, unless otherwise mutually agreed upon by the parties to the relevant Interconnection Application, shall be certified to IEEE 1547- 2018 requirements beginning February 1, 2023 (“Certification Deadline Date”) using the Company’s equipment certification process described in the Interconnection Guidebook at the time of the Interconnection Application. Non-inverter-based Generating Facilities are required to be certified to the entirety of the IEEE 1547-2018 requirements, except as otherwise provided within this section or as indicated in the Company’s latest Source Requirements Document. Until July 1, 2021, or other time period ordered by the Hawaii Public Utilities Commission, non-inverter-based Generating Facilities may be formally certified to UL- 1741 Supplement SA using the Company’s Source Requirements Document version 1.1 with any modifications to accommodate non-inverter-based generation by mutual consent between the Customer-Generator and the Company. The non-inverter requirements are intended to be consistent with ANSI/IEEE 1547- 2018 Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces. In the event of conflict between this Rule and IEEE 1547-2018, this Rule shall take precedence. Refer to the Company’s latest Source Requirements Document for equipment certification for all certification exceptions to IEEE 1547-2018 and to the Company’s latest URP for default settings. The applicable URP will be assigned to the Generating Facility by the Company as the result of the application technical reviews or Interconnection Requirements Study, or other mutually agreed upon method between the partis to the relevant interconnection agreement The URP is determined from URP’s approved by the Hawaii Public Utilities Commission. Updates to the URP’s will be hosted on the Company’s website and will occur no more frequently than annually. Generating Facility settings different than the URP shall be allowable with mutual agreement HAWAIIAN ELECTRIC COMPANY, INC.
Lines changed: 54 additions & 0 deletions
Original file line numberDiff line numberDiff line change
@@ -0,0 +1,54 @@
1+
Source: https://www.pge.com/tariffs/assets/pdf/tariffbook/ELEC_RULES_21.pdf
2+
Publisher: Pacific Gas and Electric Company, Electric Rule No. 21 (Generating Facility Interconnections), Section Hh, Smart Inverter Generating Facility Design and Operating Requirements for UL1741SB Inverters, Advice 7692-E, effective August 29, 2025
3+
Retrieved: 2026-11-21
4+
Original: 26422475 bytes, SHA-256 76768f26a08fd5760c4727832b2d538ee8e3c0144a18836f508f3f143f0bfe9f
5+
Capture: Section Hh's opening paragraph and Tables Hh-2a, Hh-3, and Hh-4 and the volt-watt paragraph, as pdftotext -layout reads them, revision marks removed and whitespace collapsed. Tables Hh-1a and Hh-1b are images on the sheet and have no text to capture.
6+
----
7+
[Rule 21 Hh, opening paragraph]
8+
The inverter requirements are intended to be consistent with UL 1741 – Supplement SB using as the source requirement document ANSI/IEEE 1547- 2018 and IEEE 1547.1-2020 Standard for Interconnecting Distributed Resources with Electric Power Systems where possible. In the event of conflict between this Rule and UL 1741 – Supplement SB and/or IEEE 1547-2018 or IEEE 1547.1-2020, this Rule shall take precedence. The Smart Inverter default settings and default activation states may be modified upon mutual agreement between Applicant or Producer and Distribution Provider.
9+
10+
[Rule 21 Hh-2a, Table Hh-2a: Frequency Trip Settings Table, Cal. P.U.C. Sheet No. 60226-E]
11+
Table Hh-2a: Frequency Trip Settings Table
12+
Shall Trip Function Frequency Trip Resulting Default Clearing
13+
Default Setting Range of Shall Time (s)
14+
(Hz) Trip Function
15+
(Hz)
16+
OF2 62.0 f≥62.0 0.16
17+
OF1 61.2 61.2≤f<62 300
18+
Continuous NA 58.5<f<61.2 NA
19+
Operation
20+
UF1 58.5 56.5<f≤58.5 300
21+
UF2 56.5 f≤56.5 0.16
22+
23+
[Rule 21 Hh, Table Hh-3: Voltage and Reactive Default Settings]
24+
Table Hh-3: Voltage and Reactive Default Settings
25+
Voltage Voltage Reactive Reactive
26+
Setpoint Value Setpoint Value Operation
27+
V1 92.0% Q1 30% Reactive Power Injection
28+
V2 97.0% Q2 0 Unity Power Factor
29+
V3 103.0% Q3 0 Unity Power Factor
30+
V4 107.0% Q4 30% Reactive Power Absorption
31+
32+
[Rule 21 Hh, volt-watt paragraph]
33+
When the measured voltage is greater than 106% of nominal voltage (Example: 127.2 volts on a 120 volts nominal), the export of active power at the PCC or the production of active power by the Smart Inverter shall be reduced at a rate of 25% of active power nameplate rating per one percent of nominal voltage. Figure Hh-3 Volt-Watt Requirements illustrate the required rate of reduction. When export of active power is controlled, a certified inverter and control system shall be used.
34+
35+
[Rule 21 Hh, Table Hh-4: Default Activation States]
36+
Table Hh-4: Default Activation States
37+
Function State
38+
Anti-islanding Activated
39+
Low/High Voltage Ride Through Activated
40+
Low/High Frequency Ride Through Activated
41+
Dynamic Volt/Var operations Activated
42+
Enter Service Ramp Control Activated
43+
Storage Inverter Normal Operation Ramp Deactivated*
44+
Control
45+
Fixed power factor Deactivated
46+
Reconnect by “soft-start” methods Activated
47+
Frequency/Watt Activated
48+
Volt/Watt Activated
49+
Constant Reactive Power Mode Deactivated
50+
Set Active Power Function Mode(Optional) Activated under
51+
mutual agreement
52+
Dynamic Reactive Power Support Mode Activated under
53+
(Optional) mutual agreement
54+
These default activation states may be modified by mutual agreement

‎data/curated/inverter-settings.mjs‎

Lines changed: 71 additions & 0 deletions
Original file line numberDiff line numberDiff line change
@@ -0,0 +1,71 @@
1+
// The certification and settings reference (add-interconnection-screens 5.5; interconnect/equipment-reference):
2+
// what each certification generation means and which rule calls for which, and the common grid-support
3+
// defaults as facts, each cited to a state rule that publishes the value, grouped by what a setting does for a
4+
// project rather than by any standard's tables. Nothing here reproduces IEEE 1547's text, tables, or numbering;
5+
// a value with no free source is omitted with the standard and section where it is defined.
6+
7+
const PGE = { publisher: 'Pacific Gas and Electric Company', document: 'Electric Rule No. 21, Section Hh (Advice 7692-E, effective 2025-08-29)', url: 'https://www.pge.com/tariffs/assets/pdf/tariffbook/ELEC_RULES_21.pdf', capture: 'data/curated/captures/interconnect/pge-rule-21-hh.txt' };
8+
const HECO = { publisher: 'Hawaiian Electric Company', document: 'Rule No. 14, Appendix I', url: 'https://www.hawaiianelectric.com/documents/billing_and_payment/rates/hawaiian_electric_rules/14.pdf', capture: 'data/curated/captures/interconnect/heco-rule-14-appendix-i-settings.txt' };
9+
10+
export const CHECKED = '2026-11-21';
11+
12+
/** The certification generations, in our words, each sentence resting on the cited text. */
13+
export const CERTIFICATION = {
14+
explained: [
15+
'UL 1741 Supplement SB is the certification that tests an inverter against IEEE 1547-2018, the current interconnection standard, using its test procedures in IEEE 1547.1-2020. California\'s Rule 21 writes its smart-inverter requirements to be consistent with SB, with IEEE 1547-2018 as the source requirement document, and says the Rule prevails where they conflict.',
16+
'UL 1741 Supplement SA is the earlier supplement, certified against a utility\'s own source requirements document rather than IEEE 1547-2018. Hawaiian Electric\'s Rule 14, for example, let non-inverter-based facilities certify to SA against its Source Requirements Document version 1.1 until July 1, 2021, and has required inverter-based facilities to be certified to IEEE 1547-2018 since February 1, 2023.',
17+
],
18+
mismatch: 'Equipment certified to the earlier SA supplement may not meet a rule that calls for IEEE 1547-2018 or UL 1741 SB: the tests and the settings it was certified to differ. Whether a particular unit is accepted, with a firmware update or a recertification or not at all, is for the authority having jurisdiction and the utility to decide.',
19+
cites: [{ ...PGE, locator: 'Section Hh, opening paragraph', quote: 'consistent with UL 1741 – Supplement SB using as the source requirement document ANSI/IEEE 1547- 2018' }, { ...HECO, locator: 'Appendix I, equipment certification', quote: 'shall be certified to IEEE 1547- 2018 requirements beginning February 1, 2023' }],
20+
};
21+
22+
/** Published defaults, grouped by what they do, each value cited to the sheet that prints it. */
23+
export const SETTINGS = [
24+
{
25+
id: 'frequency-trip', jurisdiction: 'CA', group: 'When the inverter must stop on abnormal frequency',
26+
cite: { ...PGE, locator: 'Table Hh-2a, Cal. P.U.C. Sheet No. 60226-E' },
27+
rows: [
28+
{ what: 'High frequency, fast', value: 'at or above 62.0 Hz, within 0.16 s', numbers: ['62.0', '0.16'] },
29+
{ what: 'High frequency, slow', value: 'from 61.2 Hz up to 62 Hz, within 300 s', numbers: ['61.2', '300'] },
30+
{ what: 'Low frequency, slow', value: 'from 56.5 Hz up to 58.5 Hz, within 300 s', numbers: ['58.5', '56.5<f≤58.5'] },
31+
{ what: 'Low frequency, fast', value: 'at or below 56.5 Hz, within 0.16 s', numbers: ['56.5', 'f≤56.5'] },
32+
],
33+
},
34+
{
35+
id: 'volt-var', jurisdiction: 'CA', group: 'How the inverter helps hold voltage: reactive power by voltage (volt-VAR)',
36+
cite: { ...PGE, locator: 'Table Hh-3' },
37+
rows: [
38+
{ what: 'At 92% of nominal voltage and below', value: 'inject reactive power, 30%', numbers: ['92.0%', '30%'] },
39+
{ what: 'From 97% to 103% of nominal voltage', value: 'unity power factor (no reactive power)', numbers: ['97.0%', '103.0%'] },
40+
{ what: 'At 107% of nominal voltage and above', value: 'absorb reactive power, 30%', numbers: ['107.0%', '30%'] },
41+
],
42+
},
43+
{
44+
id: 'volt-watt', jurisdiction: 'CA', group: 'When it cuts output on high voltage (volt-watt)',
45+
cite: { ...PGE, locator: 'Section Hh, volt-watt paragraph' },
46+
rows: [{ what: 'Above 106% of nominal voltage', value: 'reduce active power by 25% of nameplate for each 1% of nominal voltage', numbers: ['106%', '25%'] }],
47+
},
48+
{
49+
id: 'activation', jurisdiction: 'CA', group: 'Which functions are on by default',
50+
cite: { ...PGE, locator: 'Table Hh-4' },
51+
rows: [
52+
{ what: 'On', value: 'anti-islanding; voltage and frequency ride-through; volt-VAR; enter-service ramp; soft-start reconnection; frequency-watt; volt-watt', numbers: ['Anti-islanding Activated', 'Volt/Watt Activated', 'Frequency/Watt Activated'] },
53+
{ what: 'Off', value: 'fixed power factor; constant reactive power; the storage inverter\'s normal-operation ramp (unless agreed)', numbers: ['Fixed power factor Deactivated', 'Constant Reactive Power Mode Deactivated'] },
54+
],
55+
},
56+
];
57+
58+
/** A jurisdiction whose rule points elsewhere for its settings. */
59+
export const POINTS_ELSEWHERE = [
60+
{
61+
jurisdiction: 'HI', utility: 'Hawaiian Electric',
62+
says: 'Rule 14 requires certification to IEEE 1547-2018 and publishes no settings table of its own: default settings come from the Company\'s Utility-Required Profile, a file of configuration parameters drawn from ranges the Hawaii PUC approved, assigned to each facility and posted on the Company\'s website. California\'s numbers are not Hawaii\'s and are not shown for it.',
63+
cite: { ...HECO, locator: 'Appendix I, definition y and equipment certification', quote: 'to the Company’s latest URP for default settings' },
64+
},
65+
];
66+
67+
/** Parameters with no free, citable source as text: named, never guessed. */
68+
export const OMITTED = [
69+
{ what: 'Voltage trip and ride-through settings (how far voltage may stray, and for how long, before the inverter must stop or must keep running)', where: 'IEEE 1547-2018, the voltage trip tables for each abnormal-performance category', why: 'California prints them in Rule 21 Tables Hh-1a and Hh-1b as images on the sheet, with no text we can check against; we omit them rather than retype numbers from a picture.' },
70+
{ what: 'Reactive power capability by category (how much reactive power an inverter must be able to supply)', where: 'IEEE 1547-2018, Section 5.2 (Rule 21 calls for Category B)', why: 'No free government source prints the capability values as text.' },
71+
];

‎data/curated/published-urls.json‎

Lines changed: 1 addition & 0 deletions
Original file line numberDiff line numberDiff line change
@@ -100,6 +100,7 @@
100100
"/files/",
101101
"/grid/",
102102
"/interconnect/hosting-capacity/",
103+
"/interconnect/inverter-settings/",
103104
"/large-load/terms/",
104105
"/learn/",
105106
"/learn/balancing-authority/",

‎openspec/changes/add-interconnection-screens/tasks.md‎

Lines changed: 1 addition & 1 deletion
Original file line numberDiff line numberDiff line change
@@ -37,7 +37,7 @@
3737
- [x] 5.2 Map returned items to the screens they settle; verify the what-the-fee-buys scenario (core/lib/pre-application.mjs, labeled as our reading of § 1.2.3 beside § 2.2.1, with the model-only screens named; verify/tests/site/pre-application.test.mjs)
3838
- [x] 5.3 Build the hosting-capacity directory with terms, vintages, and per-feeder minimum-load availability, linking only; verify the viewer-only, utility-publishes-minimum-load, atlas-condition, and nothing-hosted scenarios (data/curated/hosting-capacity.mjs holds 36 utilities from docs/research/12 § 5.3, every address resolved and loaded again on 2026-11-21: access, what the terms say about reuse, and for Xcel Minnesota and Colorado and Portland General how to find a feeder's published minimum load, with no value held; Duke's maps were not found on the recheck and say so; /interconnect/hosting-capacity/ links each map and the federal atlas with its January 2026 date and condition, and the fast-track and minimum-load screen pages link the directory; verify/tests/site/hosting-capacity.test.mjs. Seven utilities' map pages are built by script, so only their landing pages are linked)
3939
- [x] 5.4 Add the map caveats and freshness chips; verify the caveat and stale-entry scenarios (the three limits, estimate, not a reservation, and changes with the queue, come before any map link; each entry shows a needs-review chip with its last-checked date a year after the check, revealed on the device; the weekly link check reads every directory link; verify/tests/site/hosting-capacity.test.mjs and verify/tests/browser/hosting-capacity.test.mjs)
40-
- [ ] 5.5 Write the certification and settings reference with per-value citations; verify the certification-mismatch, setting-cited, and no-free-source scenarios
40+
- [x] 5.5 Write the certification and settings reference with per-value citations; verify the certification-mismatch, setting-cited, and no-free-source scenarios (data/curated/inverter-settings.mjs and /interconnect/inverter-settings/: UL 1741 SB against SA, cited to PG&E's Rule 21 § Hh and Hawaiian Electric's Rule 14 Appendix I, with the decision left to the authority having jurisdiction and the utility; California's frequency trip, volt-VAR, volt-watt, and default activation settings in our own grouping, each value found in the stored capture of the Rule 21 sheet it cites; Hawaii's rule points to its Utility-Required Profile and gets no California numbers; voltage trip and ride-through, printed in Rule 21 only as images, and reactive capability by category are omitted with where IEEE 1547-2018 defines them; the inverter sizing tool links the page; verify/tests/site/inverter-settings.test.mjs and verify/tests/browser/hosting-capacity.test.mjs)
4141
- [x] 5.6 Implement inverter sizing and the export-limiting explainer; verify the 1.25 ratio, benchmarks-deferred, limited-export, and busbar scenarios (EIA's inverter-loading-ratio range read from the primary, so the research's unverified tag is cleared; Texas § 25.211(g)(1) read from the rule as the export-tested provision)
4242

4343
## 6. Surfaces

‎site/build.mjs‎

Lines changed: 4 additions & 0 deletions
Original file line numberDiff line numberDiff line change
@@ -26,6 +26,8 @@ import { CSV_COLUMNS as SCREEN_CSV_COLUMNS } from '../core/lib/screen-compare.mj
2626
import { GROUND_TRUTH_PATH, LIMITS, checkPublications, coverage as groundTruthCoverage, groundTruthCsv, groundTruthJson, loadGroundTruth } from './entities/ground-truth.mjs';
2727
import { groundTruthPage } from './templates/ground-truth.mjs';
2828
import { HC_PATH, hostingCapacityPage } from './templates/hosting-capacity.mjs';
29+
import { SETTINGS_PATH, inverterSettingsPage } from './templates/inverter-settings.mjs';
30+
import * as INVERTER_SETTINGS from '../data/curated/inverter-settings.mjs';
2931
import HOSTING_CAPACITY, { ATLAS as HC_ATLAS } from '../data/curated/hosting-capacity.mjs';
3032
import { SCORECARD_PATH, scorecardPage } from './templates/scorecard.mjs';
3133
import { loadScorecard, ratesCsv, resultsCsv, scorecardJson } from '../pipeline/lib/scorecard-files.mjs';
@@ -347,6 +349,8 @@ export async function build(opts = {}) {
347349
writeFileSync(join(outDir, SCORECARD_PATH, 'scorecard.json'), JSON.stringify(scorecardJson(sc, LIMITS), null, 2) + '\n');
348350
writeFileSync(join(outDir, SCORECARD_PATH, 'results.csv'), resultsCsv(sc.card));
349351
writeFileSync(join(outDir, SCORECARD_PATH, 'rates.csv'), ratesCsv(sc.card));
352+
// The certification and settings reference, each value cited to the rule sheet that prints it.
353+
write(SETTINGS_PATH, inverterSettingsPage({ data: INVERTER_SETTINGS, i18n }));
350354
// The hosting-capacity directory: links and descriptions only, never a value from a map.
351355
write(HC_PATH, hostingCapacityPage({ entries: HOSTING_CAPACITY, atlas: HC_ATLAS, i18n }));
352356
// The glossary, as a page and as data agents read with the same words.

‎site/strings/en-US.mjs‎

Lines changed: 14 additions & 0 deletions
Original file line numberDiff line numberDiff line change
@@ -1955,6 +1955,20 @@ export default {
19551955
'plans.programApplied': '{name}: {amount} off a year, as its tariff sheet states.',
19561956
'plans.programAdded': '{name}: its added baseline kWh are in this cost.',
19571957
'plans.programNot': '{name} not applied: {why}.',
1958+
'inv.title': 'Inverter certification and default settings',
1959+
'inv.description': 'Which inverter certification a rule calls for, and the grid-support defaults state rules publish, each cited to the sheet that prints it.',
1960+
'inv.intro': 'Which certification your inverter needs, and the grid-support defaults a state rule publishes, grouped by what each setting does for your project. Every value cites the rule sheet that prints it.',
1961+
'inv.notReproduced': 'IEEE 1547\'s own text, tables, and numbering are not reproduced here. These are facts as state rules publish them, in our own grouping.',
1962+
'inv.certTitle': 'Which certification',
1963+
'inv.mismatchLead': 'If your equipment carries the earlier certification:',
1964+
'inv.source': 'Source:',
1965+
'inv.defaultsTitle': 'Published defaults',
1966+
'inv.defaultsIntro': 'California writes these defaults into its tariff. A utility may agree different settings for a project, and other states may differ.',
1967+
'inv.elsewhereTitle': 'Where a state\'s rule points elsewhere',
1968+
'inv.omittedTitle': 'Not given here, and why',
1969+
'inv.definedIn': 'Defined in {where}.',
1970+
'inv.checked': 'Read from the rules on {date}.',
1971+
'inv.link': 'Inverter certification and the default settings state rules publish',
19581972
'hc.title': 'Hosting-capacity maps, by utility',
19591973
'hc.description': 'Which utilities publish a hosting-capacity map, whether its data downloads, who publishes feeder minimum load, and what their terms allow. Links only.',
19601974
'hc.intro': 'Where each utility\'s hosting-capacity map is, whether you can download its data, whether it publishes a feeder\'s minimum load (what the 100% supplemental screen needs), and what its terms say about reuse. We link to each map and copy nothing from it.',

0 commit comments

Comments
 (0)