230 changes: 230 additions & 0 deletions profiles/Eddy-Solutions/Eddy-Solutions-Link.yaml
Original file line number Diff line number Diff line change
@@ -0,0 +1,230 @@
codec: |
function readUint16(bytes, offset) {
return bytes[offset] * 0x100 + bytes[offset + 1];
}

function readUint32(bytes, offset) {
return bytes[offset] * 0x1000000 +
bytes[offset + 1] * 0x10000 +
bytes[offset + 2] * 0x100 +
bytes[offset + 3];
}

function payloadBytesAreValid(bytes) {
if (!Array.isArray(bytes) || bytes.length === 0 || bytes.length > 255) {
return false;
}
for (var index = 0; index < bytes.length; index += 1) {
if (!Number.isInteger(bytes[index]) || bytes[index] < 0 || bytes[index] > 255) {
return false;
}
}
return true;
}

function frameLengthIsValid(type, length) {
// Uplink field layouts: Link Meter Technical Specification sections 4.1-4.9.
if (type === 0x01) {
return length === 9;
}
if (type === 0x02) {
return length >= 11;
}
if (type === 0x82) {
return length >= 5;
}
if (type === 0x03) {
return length === 3;
}
if (type === 0x04) {
return length >= 3;
}
if (type === 0x15) {
return length === 8;
}
return false;
}

function validateFrame(fPort, bytes) {
if (fPort !== 3) {
return "unsupported fPort";
}
if (!payloadBytesAreValid(bytes)) {
return "invalid payload";
}
if (!frameLengthIsValid(bytes[0], bytes.length)) {
return "invalid payload length for message type";
}
return null;
}

function appendMeterStatus(values, bytes, offset) {
// Valve operation codes (meter status byte 0, bits 5-7):
// 0 = steady state, 1 = button pressed, 2 = cloud command, 3 = automatic shut-off.
var operation = (bytes[offset] >> 5) & 0x07;
// Valve state codes (meter status byte 1, bits 0-2):
// 0 = closed, 1 = opening, 2 = closing, 3 = open, 4 = error.
var valve = bytes[offset + 1] & 0x07;
// Flow alert bits (meter status byte 1): bit 3 = minor, bit 4 = major, bit 5 = extreme.
var alerts = bytes[offset + 1];

values.push({ name: "Valve Operation Status", channel: 5, value: operation, unit: null });
values.push({ name: "Valve Status", channel: 6, value: valve, unit: null });
values.push({ name: "Minor Flow Alert", channel: 7, value: (alerts >> 3) & 0x01, unit: null });
values.push({ name: "Major Flow Alert", channel: 8, value: (alerts >> 4) & 0x01, unit: null });
values.push({ name: "Extreme Flow Alert", channel: 9, value: (alerts >> 5) & 0x01, unit: null });
}

function Decode(fPort, data, variables) {
if (validateFrame(fPort, data) !== null) {
return [];
}

var values = [];
var type = data[0];

if (type === 0x01) {
// Describe byte 5 carries the report period in minutes; the same parameter is
// writable through the 0x71 downlink command on channel 11.
var reportPeriod = data[5];
// Firmware version is preserved as the documented 16-bit protocol code (0x0702).
values.push({ name: "Report Period", channel: 3, value: reportPeriod, unit: "minutes" });
values.push({ name: "Firmware Version", channel: 4, value: readUint16(data, 1), unit: null });
values.push({ name: "Set Report Period", channel: 11, value: reportPeriod, unit: "minutes" });
return values;
}

if (type === 0x02) {
values.push({ name: "Flow Rate", channel: 1, value: readUint16(data, 9), unit: null });
values.push({ name: "Odometer", channel: 2, value: readUint32(data, 3), unit: null });
appendMeterStatus(values, data, 1);
return values;
}

if (type === 0x82) {
values.push({ name: "Flow Rate", channel: 1, value: readUint16(data, 3), unit: null });
return values;
}

if (type === 0x03) {
appendMeterStatus(values, data, 1);
return values;
}

if (type === 0x04) {
if (data.length >= 11) {
values.push({ name: "Flow Rate", channel: 1, value: readUint16(data, 9), unit: null });
}
if (data.length >= 7) {
values.push({ name: "Odometer", channel: 2, value: readUint32(data, 3), unit: null });
}
appendMeterStatus(values, data, 1);
return values;
}

if (type === 0x15) {
appendMeterStatus(values, data, 6);
return values;
}

return values;
}

function Encode(data, variables) {
if (!data || !Number.isInteger(data.channel) || typeof data.value !== "number" || !Number.isFinite(data.value)) {
return [];
}

// Valve Control (0x73): 0x00 opens the valve, 0x01 closes the valve.
if (data.channel === 10 && (data.value === 0 || data.value === 1)) {
return [0x73, data.value];
}

// Meter Report Period (0x71): 0x00 test mode, 0x01 minute mode, 0x02-0x3C batch mode.
if (data.channel === 11 && Number.isInteger(data.value) && data.value >= 0 && data.value <= 60) {
return [0x71, data.value];
}

return [];
}

function decodeUplink(input) {
if (!input || !Array.isArray(input.bytes)) {
return { data: [], errors: ["invalid input"] };
}
var error = validateFrame(input.fPort, input.bytes);
if (error !== null) {
return { data: [], errors: [error] };
}
return { data: Decode(input.fPort, input.bytes, input.variables) };
}

function encodeDownlink(input) {
if (!input) {
return { bytes: [], errors: ["invalid input"] };
}
var bytes = Encode(input.data, input.variables);
if (bytes.length === 0) {
return { bytes: [], errors: ["unsupported channel or value"] };
}
return { bytes: bytes, fPort: 5 };
}
datatype:
"1":
name: Flow Rate
type: AnalogInputObject
channel: 1
"2":
name: Odometer
type: AnalogValueObject
channel: 2
"3":
name: Report Period
type: AnalogValueObject
units: minutes
channel: 3
"4":
name: Firmware Version
type: AnalogValueObject
channel: 4
"5":
name: Valve Operation Status
type: AnalogInputObject
channel: 5
"6":
name: Valve Status
type: AnalogInputObject
channel: 6
"7":
name: Minor Flow Alert
type: BinaryInputObject
channel: 7
"8":
name: Major Flow Alert
type: BinaryInputObject
channel: 8
"9":
name: Extreme Flow Alert
type: BinaryInputObject
channel: 9
"10":
name: Valve Control
type: BinaryOutputObject
fport: 5
channel: 10
"11":
name: Set Report Period
type: AnalogValueObject
units: minutes
fport: 5
channel: 11
lorawan:
macVersion: LORAWAN_1_0_4
supportClassB: false
supportClassC: true
supportOTAA: true
model: Eddy-Solutions-Link
profileVersion: 1.0.0
name: Link
vendor: Eddy-Solutions
id: 06ac414a-7a58-4dea-b58d-f5055d1d27fb
107 changes: 107 additions & 0 deletions profiles/Eddy-Solutions/tests/Eddy-Solutions-Link.test.json
Original file line number Diff line number Diff line change
@@ -0,0 +1,107 @@
{
"schemaVersion": 1,
"strict": true,
"profile": "Eddy-Solutions-Link",
"evidenceLevel": "known-answer",
"reviewMode": "single-model",
"fPortPolicy": {
"mode": "fixed",
"ports": [3],
"citation": "Issue #42 declares fport3 on all three uplink examples; its downlink command examples declare Fport 5, which datatype channels 10 and 11 declare as fport."
},
"sources": [
{
"type": "issue",
"reference": "Issue #42 uplink examples",
"citation": "fport3: 010702080319180102 (Describe), 020C040000001C0104B000 (Meter Data), 030800 (Valve)"
},
{
"type": "issue",
"reference": "Issue #42 downlink command vectors",
"citation": "Fport 5: Close Valve value 1 -> 0x7301, Open Valve value 0 -> 0x7300, Set Report Period value 5 -> 0x7105"
},
{
"type": "official-document",
"reference": "Link Meter Technical Specification v1.0 (15 pages)",
"citation": "Sections 4.1-4.2.1 uplink layouts and meter status bits; sections 5.2 and 5.4 downlink commands"
}
],
"robustness": {
"checkTruncation": true,
"checkUnknownFPort": true,
"checkFuzz": true
},
"testCases": [
{
"name": "Describe (0x01) firmware version and report period",
"messageType": "0x01",
"fPort": 3,
"input": "010702080319180102",
"description": "Issue #42 Describe frame: firmware version bytes 1-2 = 0x0702 = 1794, report period byte 5 = 0x19 = 25 minutes.",
"expectedOutput": [
{ "name": "Report Period", "channel": 3, "value": 25, "unit": "minutes" },
{ "name": "Firmware Version", "channel": 4, "value": 1794, "unit": null },
{ "name": "Set Report Period", "channel": 11, "value": 25, "unit": "minutes" }
]
},
{
"name": "Meter Data (0x02) flow rate, odometer and meter status",
"messageType": "0x02",
"fPort": 3,
"input": "020C040000001C0104B000",
"description": "Issue #42 Meter Data frame: odometer bytes 3-6 = 28, flow rate bytes 9-10 = 0xB000 = 45056, meter status 0x0C04 -> steady state, valve error, no flow alerts.",
"expectedOutput": [
{ "name": "Flow Rate", "channel": 1, "value": 45056, "unit": null },
{ "name": "Odometer", "channel": 2, "value": 28, "unit": null },
{ "name": "Valve Operation Status", "channel": 5, "value": 0, "unit": null },
{ "name": "Valve Status", "channel": 6, "value": 4, "unit": null },
{ "name": "Minor Flow Alert", "channel": 7, "value": 0, "unit": null },
{ "name": "Major Flow Alert", "channel": 8, "value": 0, "unit": null },
{ "name": "Extreme Flow Alert", "channel": 9, "value": 0, "unit": null }
]
},
{
"name": "Valve (0x03) meter status",
"messageType": "0x03",
"fPort": 3,
"input": "030800",
"description": "Issue #42 Valve frame: meter status 0x0800 -> steady state, valve closed, no flow alerts.",
"expectedOutput": [
{ "name": "Valve Operation Status", "channel": 5, "value": 0, "unit": null },
{ "name": "Valve Status", "channel": 6, "value": 0, "unit": null },
{ "name": "Minor Flow Alert", "channel": 7, "value": 0, "unit": null },
{ "name": "Major Flow Alert", "channel": 8, "value": 0, "unit": null },
{ "name": "Extreme Flow Alert", "channel": 9, "value": 0, "unit": null }
]
}
],
"downlinkTestCases": [
{
"name": "Close Valve",
"channel": 10,
"value": 1,
"expectedFPort": 5,
"expectedBytes": "73 01",
"description": "Issue #42 vector: Close Valve, Fport 5, control value 0x01, expected downlink 0x7301.",
"citation": "Issue #42 downlink evidence and specification section 5.4 (0x01 close valve)"
},
{
"name": "Open Valve",
"channel": 10,
"value": 0,
"expectedFPort": 5,
"expectedBytes": "73 00",
"description": "Issue #42 vector: Open Valve, Fport 5, control value 0x00, expected downlink 0x7300.",
"citation": "Issue #42 downlink evidence and specification section 5.4 (0x00 open valve)"
},
{
"name": "Set Report Period",
"channel": 11,
"value": 5,
"expectedFPort": 5,
"expectedBytes": "71 05",
"description": "Issue #42 vector: Set Report Period, Fport 5, control value 0x05, expected downlink 0x7105.",
"citation": "Issue #42 downlink evidence and specification section 5.2 (0x02-60 batch mode minutes)"
}
]
}
Loading